Product Details
This switch is suitable for three-phase and single-phase oil-immersed power transformers with rated voltages of 12, 24, or 40.5 kV, operating at frequencies of 50 or 60 Hz, and rated currents ranging from 20 to 300 A. It offers two tap‑changing configurations—central tap and neutral‑point tap—and can be directly mounted on the transformer tank cover or tank wall. Tap changes are performed under no‑excitation conditions.
| Switch Model (A) | Rated Current (A) | Maximum Equipment Voltage (kV) | Voltage regulation range | Number of phases | Pressure-regulating section | Installation dimensions (mm) | Hole in the box lid (mm) | |||||||||
| Type of tap-changer | Rated current (A) | Highest voltage for equipment(kV) | Range of voltage regulation | No. of phases | Regulating Position | H | H1 | H2 | L | L1 | L2 | L3 | L4 | I | Md | Holes on tank cover(mm) |
| WDT II 63/12-4×3 | 63 | 12 | ±5% | 1 | Middle part | 180 | 96 | 75 | 255 | 147 | 98 | 65 | 97 | 24 | M6 | Φ43 |
| WDT II 125/12-4×3 | 125 | ±5% | 185 | 100 | 75 | 280 | 162 | 108 | 68 | 104 | 29 | M8 | ||||
| WDT II 250/12-4×3 | 250 | ±5% | 185 | 100 | 75 | 315 | 177 | 128 | 78 | 120 | 34 | M10 | ||||
| WDT II 63/12-6×5 | 63 | ±2×2.5% | 180 | 96 | 75 | 351 | 195 | 146 | 65 | 97 | 24 | M6 | ||||
| WDT II 125/12-6×5 | 125 | ±2×2.5% | 185 | 100 | 75 | 396 | 220 | 166 | 68 | 104 | 29 | M8 | ||||
| WDT II 250/12-6×5 | 250 | ±2×2.5% | 185 | 100 | 75 | 451 | 245 | 196 | 78 | 120 | 34 | M10 | ||||
| WDT II 63/40.5-4×3 | 63 | 40.5 | ±5% | 200 | 116 | 95 | 335 | 212 | 113 | 65 | 101 | 24 | M6 | |||
| WDT II 125/40.5-4×3 | 125 | ±5% | 205 | 120 | 95 | 351 | 227 | 114 | 68 | 110 | 29 | M8 | ||||
| WDT II 250/40.5-4×3 | 250 | ±5% | 205 | 120 | 95 | 380 | 242 | 128 | 78 | 124 | 34 | M10 | ||||
| WDT II 63/40.5-6×5 | 63 | ±2×2.5% | 200 | 116 | 95 | 431 | 260 | 161 | 65 | 101 | 24 | M6 | ||||
| WDT II 125/40.5-6×5 | 125 | ±2×2.5% | 205 | 120 | 95 | 467 | 285 | 172 | 68 | 110 | 29 | M8 | ||||
| WDT II 250/40.5-6×5 | 250 | ±2×2.5% | 205 | 120 | 95 | 516 | 310 | 196 | 78 | 124 | 34 | M10 | ||||
| WST II 63/12-4×3 Medium Size | 63 | 12 | ±5% | 3 | 180 | 96 | 75 | 396 | 142 | 132 | 54 | 88 | 24 | M6 | ||
| WST Ⅱ 63/12-4×3 | 63 | ±5% | 180 | 96 | 75 | 396 | 142 | 132 | 58 | 97 | 24 | M6 | ||||
| WST II 125/12-4×3 Medium Size | 125 | ±5% | 185 | 100 | 75 | 441 | 158 | 147 | 54 | 88 | 29 | M8 | ||||
| WST Ⅱ 125/12-4×3 | 125 | ±5% | 185 | 100 | 75 | 441 | 158 | 147 | 58 | 105 | 29 | M8 | ||||
| WST Ⅱ 250/12-4×3Z | 250 | ±5% | 185 | 100 | 75 | 576 | 217 | 207 | 68 | 120 | 34 | M10 | ||||
| WST Ⅱ 300/12-4×3Z | 300 | ±5% | 185 | 100 | 75 | 576 | 217 | 207 | 68 | 128 | 34 | M12 | ||||
| WST II 63/12-6×5 Medium Size | 63 | ±2×2.5% | 180 | 96 | 75 | 540 | 190 | 180 | 54 | 88 | 24 | M6 | ||||
| WST Ⅱ 63/12-6×5 | 63 | ±2×2.5% | 180 | 96 | 75 | 540 | 190 | 180 | 58 | 97 | 24 | M6 | ||||
| WST II 125/12-6×5 Medium Size | 125 | ±2×2.5% | 185 | 100 | 75 | 615 | 216 | 205 | 58 | 95 | 29 | M8 | ||||
| WST Ⅱ 125/12-6×5 | 125 | ±2×2.5% | 185 | 100 | 75 | 615 | 216 | 205 | 58 | 105 | 29 | M8 | ||||
| WST Ⅱ 250/12-6×5Z | 250 | ±2×2.5% | 185 | 100 | 75 | 780 | 285 | 275 | 68 | 120 | 34 | M10 | ||||
| WST Ⅱ 300/12-6×5Z | 300 | ±2×2.5% | 185 | 100 | 75 | 780 | 285 | 275 | 68 | 128 | 34 | M12 | ||||
| WST Ⅳ 63/12-3×2Y-Δ | 63 | ±3×2.5% | Y-Δ | 185 | 100 | 75 | 610 | 216 | 200 | 58 | 101 | 70 | M6 | |||
| WST Ⅳ 125/12-3×2Y-Δ | 125 | ±3×2.5% | 185 | 100 | 75 | 610 | 216 | 200 | 58 | 105 | 70 | M8 | ||||
| WST Ⅱ 63/12-8×7 | 63 | ±3×2.5% | Middle part | 180 | 96 | 75 | 684 | 238 | 228 | 68 | 107 | 24 | M6 | |||
| WST Ⅱ 125/12-8×7 | 125 | ±3×2.5% | 185 | 100 | 75 | 789 | 274 | 263 | 68 | 115 | 29 | M8 | ||||
| WST Ⅱ 250/12-8×7Z | 250 | ±3×2.5% | 185 | 100 | 75 | 984 | 353 | 343 | 68 | 120 | 34 | M10 | ||||
| WST Ⅱ 63/12-9×10 | 63 | ±4×1.25% | 180 | 96 | 75 | 828 | 286 | 276 | 68 | 107 | 24 | M6 | ||||
| WST Ⅱ 63/17.5-4×3 | 63 | 17.5 | ±5% | 180 | 96 | 75 | 426 | 157 | 137 | 58 | 97 | 24 | M6 | |||
| WST Ⅱ 125/17.5-4×3 | 125 | ±5% | 185 | 100 | 75 | 471 | 173 | 152 | 58 | 105 | 29 | M8 | ||||
| WST Ⅱ 250/17.5-4×3Z | 250 | ±5% | 185 | 100 | 75 | 636 | 247 | 227 | 68 | 120 | 34 | M10 | ||||
| WST Ⅱ 63/17.5-6×5 | 63 | ±2×2.5% | 180 | 96 | 75 | 570 | 205 | 185 | 58 | 97 | 24 | M6 | ||||
| WST Ⅱ 125/17.5-6×5 | 125 | ±2×2.5% | 185 | 100 | 75 | 645 | 231 | 210 | 58 | 105 | 29 | M8 | ||||
| WST Ⅱ 250/17.5-6×5Z | 250 | ±2×2.5% | 185 | 100 | 75 | 840 | 315 | 295 | 68 | 120 | 34 | M10 | ||||
| WST Ⅱ 63/24-4×3 | 63 | 24 | ±5% | 195 | 116 | 95 | 446 | 167 | 142 | 58 | 101 | 24 | M6 | |||
| WST Ⅱ 125/24-4×3 | 125 | ±5% | 200 | 120 | 95 | 491 | 183 | 157 | 58 | 111 | 29 | M8 | ||||
| WST Ⅱ 250/24-4×3Z | 250 | ±5% | 200 | 120 | 95 | 666 | 262 | 237 | 68 | 124 | 34 | M10 | ||||
| WST Ⅱ 63/24-6×5 | 63 | ±2×2.5% | 195 | 116 | 95 | 590 | 215 | 190 | 58 | 101 | 24 | M6 | ||||
| WST Ⅱ 125/24-6×5 | 125 | ±2×2.5% | 200 | 120 | 95 | 665 | 241 | 215 | 58 | 111 | 29 | M8 | ||||
| WST Ⅱ 250/24-6×5Z | 250 | ±2×2.5% | 200 | 120 | 95 | 870 | 330 | 305 | 68 | 124 | 34 | M10 | ||||
| WST Ⅱ 63/40.5-4×3 | 63 | 40.5 | ±5% | 200 | 116 | 95 | 546 | 217 | 167 | 58 | 101 | 24 | M6 | |||
| WST Ⅱ 125/40.5-4×3 | 125 | ±5% | 205 | 120 | 95 | 591 | 233 | 182 | 58 | 111 | 29 | M8 | ||||
| WST Ⅱ 250/40.5-4×3Z | 250 | ±5% | 205 | 120 | 95 | 816 | 337 | 287 | 68 | 124 | 34 | M10 | ||||
| WST Ⅱ 300/40.5-4×3Z | 300 | ±5% | 205 | 120 | 95 | 816 | 337 | 287 | 68 | 133 | 34 | M12 | ||||
| WST Ⅱ 63/40.5-6×5 | 63 | ±2×2.5% | 200 | 116 | 95 | 690 | 265 | 215 | 58 | 101 | 24 | M6 | ||||
| WST Ⅱ 125/40.5-6×5 | 125 | ±2×2.5% | 205 | 120 | 95 | 765 | 291 | 240 | 58 | 111 | 29 | M8 | ||||
| WST Ⅱ 250/40.5-6×5Z | 250 | ±2×2.5% | 205 | 120 | 95 | 1020 | 405 | 355 | 68 | 124 | 34 | M10 | ||||
| WST Ⅱ 300/40.5-6×5Z | 300 | ±2×2.5% | 205 | 120 | 95 | 1020 | 405 | 355 | 68 | 133 | 34 | M12 | ||||
| WST Ⅱ 63/40.5-8×7 | 63 | ±3×2.5% | 200 | 116 | 95 | 834 | 313 | 269 | 68 | 111 | 24 | M6 | ||||
| WST Ⅱ 125/40.5-8×7 | 125 | ±3×2.5% | 205 | 120 | 95 | 939 | 349 | 298 | 68 | 120 | 29 | M8 | ||||
| WST Ⅱ 250/40.5-8×7Z | 250 | ±3×2.5% | 205 | 120 | 95 | 1224 | 473 | 423 | 68 | 124 | 34 | M10 | ||||
| WST Ⅱ 300/40.5-8×7Z | 300 | ±3×2.5% | 205 | 120 | 95 | 1224 | 473 | 423 | 68 | 133 | 34 | M12 | ||||
| Type of tap-changer | Rated current (A) | Highest voltage for equipment (kV) | Range of voltage regulation | Number of phases | Regulating Position | Installation dimensions (mm) | Holes on tank cover (mm) | |||||||||
| H | H1 | H2 | L | L1 | L2 | L3 | L4 | I | Md | |||||||
| WST Ⅲ 63/12-3×3 | 63 | 12 | ±5% | 3 | Neutral point | 180 | 96 | 75 | 345 | 134 | 108 | 58 | 97 | 24 | M6 | Φ43 |
| WST Ⅲ 125/12-3×3 | 125 | ±5% | 185 | 100 | 75 | 454 | 174 | 143 | 58 | 105 | 29 | M8 | ||||
| WST Ⅲ 250/12-3×3 | 250 | ±5% | 185 | 100 | 75 | 454 | 174 | 143 | 58 | 110 | 29 | M10 | ||||
| WST Ⅲ 63/12-5×5 | 63 | ±2×2.5% | 180 | 96 | 75 | 489 | 182 | 156 | 58 | 97 | 24 | M6 | ||||
| WST Ⅲ 125/12-5×5 | 125 | ±2×2.5% | 185 | 100 | 75 | 628 | 232 | 201 | 58 | 105 | 29 | M8 | ||||
| WST Ⅲ 250/12-5×5 | 250 | ±2×2.5% | 185 | 100 | 75 | 628 | 232 | 201 | 58 | 110 | 29 | M10 | ||||
| WST Ⅲ 63/12-7×7 | 63 | ±3×2.5% | 180 | 96 | 75 | 633 | 230 | 204 | 68 | 107 | 24 | M6 | ||||
| WST Ⅲ 125/12-7×7 | 125 | ±3×2.5% | 185 | 100 | 75 | 802 | 290 | 259 | 68 | 115 | 29 | M8 | ||||
| WST Ⅲ 250/12-7×7 | 250 | ±3×2.5% | 185 | 100 | 75 | 802 | 290 | 259 | 68 | 120 | 29 | M10 | ||||
| WST Ⅲ 63/24-3×3 | 63 | 24 | ±5% | 200 | 116 | 95 | 345 | 134 | 108 | 65 | 101 | 24 | M6 | |||
| WST Ⅲ 125/24-3×3 | 125 | ±5% | 205 | 120 | 95 | 454 | 174 | 143 | 67 | 110 | 29 | M8 | ||||
| WST Ⅲ 250/24-3×3 | 250 | ±5% | 205 | 120 | 95 | 454 | 174 | 143 | 67 | 114 | 29 | M10 | ||||
| WST Ⅲ 63/24-5×5 | 63 | ±2×2.5% | 200 | 116 | 95 | 489 | 182 | 156 | 65 | 101 | 24 | M6 | ||||
| WST Ⅲ 125/24-5×5 | 125 | ±2×2.5% | 205 | 120 | 95 | 628 | 232 | 201 | 67 | 110 | 29 | M8 | ||||
| WST Ⅲ 250/24-5×5 | 250 | ±2×2.5% | 205 | 120 | 95 | 628 | 232 | 201 | 67 | 114 | 29 | M10 | ||||
| WST Ⅲ 63/24-7×7 | 63 | ±3×2.5% | 200 | 116 | 95 | 633 | 230 | 204 | 76 | 111 | 24 | M6 | ||||
| WST Ⅲ 125/24-7×7 | 125 | ±3×2.5% | 205 | 120 | 95 | 802 | 290 | 259 | 78 | 120 | 29 | M8 | ||||
| WST Ⅲ 250/24-7×7 | 250 | ±3×2.5% | 205 | 120 | 95 | 802 | 290 | 259 | 78 | 124 | 29 | M10 | ||||
| WST Ⅲ 63/12-3×3A | 63 | 12 | ±5% | 180 | 96 | 75 | 501 | 411 | 477 | 65 | 97 | 24 | M6 | |||
| WST Ⅲ 125/12-3×3A | 125 | ±5% | 185 | 100 | 75 | 541 | 441 | 87 | 67 | 104 | 29 | M8 | ||||
| WST Ⅲ 63/12-5×5A | 63 | ±2×2.5% | 180 | 96 | 75 | 692 | 555 | 124 | 65 | 97 | 24 | M6 | ||||
| WST Ⅲ 125/12-5×5A | 125 | ±2×2.5% | 185 | 100 | 75 | 772 | 615 | 144 | 67 | 104 | 29 | M8 | ||||
| WST Ⅲ 63/12-7×7A | 63 | ±3×2.5% | 180 | 96 | 75 | 884 | 699 | 172 | 76 | 107 | 24 | M6 | ||||
| WST Ⅲ 125/12-7×7A | 125 | ±3×2.5% | 185 | 100 | 75 | 1012 | 789 | 210 | 78 | 114 | 29 | M8 | ||||
| WST Ⅲ 63/40.5-3×3A | 63 | 40.5 | ±5% | 200 | 116 | 95 | 501 | 411 | 77 | 65 | 101 | 24 | M6 | |||
| WST Ⅲ 125/40.5-3×3A | 125 | ±5% | 205 | 120 | 95 | 541 | 441 | 87 | 67 | 110 | 29 | M8 | ||||
| WST Ⅲ 63/40.5-5×5A | 63 | ±2×2.5% | 200 | 116 | 95 | 692 | 555 | 124 | 65 | 101 | 24 | M6 | ||||
| WST Ⅲ 125/40.5-5×5A | 125 | ±2×2.5% | 205 | 120 | 95 | 772 | 615 | 144 | 67 | 110 | 29 | M8 | ||||
| WST Ⅲ 63/40.5-7×7A | 63 | ±3×2.5% | 3 | 200 | 116 | 95 | 884 | 699 | 172 | 76 | 111 | 24 | M6 | |||
| WST Ⅲ 125/40.5-7×7A | 125 | ±3×2.5% | 3 | 205 | 120 | 95 | 1012 | 789 | 210 | 78 | 120 | 29 | M8 | |||
We can manufacture on-load tap changers with extended tank covers upon customer request.
Tap changers rated at 63 A and 125 A are suitable for transformer tank covers with thicknesses of 6 to 10 mm; tap changers rated at 250 A and 300 A are suitable for transformer tank covers with thicknesses of 8 to 12 mm.
We can manufacture the tap-changer with raised highness beneath the cover in accordance with the customer's requirement.
The current of 63A and 125A tap-changer is applicable to 6~1Omm transformer cover.
The current of 250A and 400A tap-changers are applicable to8~12mm transformer cover.
Models with a “Z” suffix feature a metal base (reinforced type).
The end of model with Z is metal seat (reinforced)
Add “F” after the original model number, e.g., WST63/40.5-65F.
The reverse,at the end of the original model add F,for example:WST Il 63/40.5-6 x 5F
Keywords:
Non-excitation strip-type tap changer
Learn more about the product
Submit your request or feedback
If you are interested in our products, please feel free to contact us to discuss potential collaboration.
Telephone
Email box
Address
No. 3 Fengming Road, Hairun Subdistrict, Sanmen County, Taizhou City, Zhejiang Province
Website Development:China Enterprise Dynamics Nantong|Tag