Product Details
The non‑excited three‑phase strip‑type series‑parallel, star‑delta conversion, and tap‑changing combined tap changers developed by our company meet the requirements for switching between different voltage levels in power transmission and transformation projects.
WST series linear form combined de-energized tap-changer
Type of tap-changer and installation size chart
Type of tap-changer and installation size chart
| Type of combined tap-changer | Rated current (A) | Highest voltage for equipment (kV) | Range of voltage regulation | Number of phases | Regulating Position | Installation dimensions (mm) | Holes on tank cover (mm) | ||||||||
| H | H1 | H2 | L | L1 | L2 | L3 | L4 | Md | |||||||
| WST Ⅳ 63/12-3×2 (Y-Δ) | 63 | 12 | ±5% | 3 | Middle part | 180 | 75 | 70 | 534 | 167 | 200 | -- | 115 | M6 | Φ43 |
| WST Ⅳ 63/12-4×3 | 63 | 12 | ±5% | 3 | Middle part | 180 | 75 | 70 | 534 | 167 | 200 | -- | 115 | M6 | |
| WST Ⅳ 63/12-3×2 (Y-Δ) | 63 | 12 | ±2×2.5% | 3 | Middle part | 180 | 75 | 70 | 570 | 185 | 280 | -- | 115 | M6 | |
| WST Ⅳ 63/12-6×5 | 63 | 12 | ±2×2.5% | 3 | Middle part | 180 | 75 | 70 | 570 | 185 | 280 | -- | 115 | M6 | |
| WST Ⅳ 63/12-8×7 | 63 | 12 | ±3×2.5% | 3 | Middle part | 180 | 75 | 70 | 814 | 258 | 298 | -- | 123 | M6 | |
| WST Ⅳ 63/12-3×2 (Y-Δ) | 63 | 12 | ±3×2.5% | 3 | Middle part | 180 | 75 | 70 | 814 | 258 | 298 | -- | 123 | M6 | |
| WST Ⅳ 125/12-3×2 (Y-Δ) | 125 | 12 | ±5% | 3 | Middle part | 185 | 75 | 70 | 750 | 235 | 280 | -- | 110 | M8 | |
| WST Ⅳ 125/12-4×3 | 125 | 12 | ±5% | 3 | Middle part | 185 | 75 | 70 | 750 | 235 | 280 | -- | 110 | M8 | |
| WST Ⅳ 125/12-3×2 (Y-Δ) | 125 | 12 | ±2×2.5% | 3 | Middle part | 185 | 75 | 70 | 756 | 238 | 280 | -- | 110 | M8 | |
| WST Ⅳ 125/12-6×5 | 125 | 12 | ±2×2.5% | 3 | Middle part | 185 | 75 | 70 | 756 | 238 | 280 | -- | 110 | M8 | |
| WST Ⅳ 125/12-3×2 (Y-Δ) | 125 | 12 | ±3×2.5% | 3 | Middle part | 185 | 75 | 70 | 894 | 287 | 320 | -- | 115 | M8 | |
| WST Ⅳ 125/12-8×7 | 125 | 12 | ±3×2.5% | 3 | Middle part | 185 | 75 | 70 | 894 | 287 | 320 | -- | 115 | M8 | |
| WST Ⅳ 250/12-3×2Z (Y-Δ) | 250 | 12 | ±5% | 3 | Middle part | 185 | 75 | 70 | 790 | 245 | 300 | -- | 120 | M10 | |
| WST Ⅳ 250/12-4×3Z | 250 | 12 | ±5% | 3 | Middle part | 185 | 75 | 70 | 790 | 245 | 300 | -- | 120 | M10 | |
| WST Ⅳ 250/12-3×2Z (Y-Δ) | 250 | 12 | ±2×2.5% | 3 | Middle part | 185 | 75 | 70 | 880 | 275 | 330 | -- | 120 | M10 | |
| WST Ⅳ 250/12-6×5Z | 250 | 12 | ±2×2.5% | 3 | Middle part | 185 | 75 | 70 | 880 | 275 | 330 | -- | 120 | M10 | |
| WST Ⅳ 250/12-3×2Z (Y-Δ) | 250 | 12 | ±3×2.5% | 3 | Middle part | 185 | 75 | 70 | 1084 | 343 | 398 | -- | 120 | M10 | |
| WST Ⅳ 250/12-8×7Z | 250 | 12 | ±3×2.5% | 3 | Middle part | 185 | 75 | 70 | 1084 | 343 | 398 | -- | 120 | M10 | |
| WST Ⅱ 63/12-4×3ZH | 63 | 12 | ±5% | 3 | Middle part | 180 | 75 | 70 | 474 | 157 | 182 | 58 | 97 | M6 | |
| WST Ⅱ 63/12-6×5ZH | 63 | 12 | ±2×2.5% | 3 | Middle part | 180 | 75 | 70 | 618 | 205 | 230 | 58 | 97 | M6 | |
| WST Ⅱ 125/12-4×3ZH | 125 | 12 | ±5% | 3 | Middle part | 185 | 75 | 70 | 519 | 172 | 197 | 58 | 105 | M8 | |
| WST Ⅱ 125/12-6×5ZH | 125 | 12 | ±2×2.5% | 3 | Middle part | 185 | 75 | 70 | 693 | 230 | 255 | 58 | 105 | M8 | |
| WST Ⅱ 250/12-4×3ZH | 250 | 12 | ±5% | 3 | Middle part | 185 | 75 | 70 | 604 | 207 | 231 | 68 | 120 | M10 | |
| WST Ⅱ 250/12-6×5ZH | 250 | 12 | ±2×2.5% | 3 | Middle part | 185 | 75 | 70 | 808 | 275 | 299 | 68 | 120 | M10 | |
| WST Ⅱ 63/24-4×3ZH | 63 | 24 | ±5% | 3 | Middle part | 210 | 95 | 80 | 486 | 157 | 187 | 58 | 101 | M6 | |
| WST Ⅱ 63/24-6×5ZH | 63 | 24 | ±2×2.5% | 3 | Middle part | 210 | 95 | 80 | 630 | 205 | 235 | 58 | 101 | M6 | |
| WST Ⅱ 125/24-4×3ZH | 125 | 24 | ±5% | 3 | Middle part | 210 | 95 | 80 | 531 | 172 | 202 | 58 | 101 | M8 | |
| WST Ⅱ 125/24-6×5ZH | 125 | 24 | ±2×2.5% | 3 | Middle part | 215 | 95 | 80 | 705 | 230 | 260 | 58 | 111 | M8 | |
| WST Ⅱ 63/40.5-4×3ZH | 63 | 40.5 | ±5% | 3 | Middle part | 210 | 95 | 80 | 546 | 167 | 216 | 58 | 101 | M6 | |
| WST Ⅱ 63/40.5-6×5ZH | 63 | 40.5 | ±2×2.5% | 3 | Middle part | 210 | 95 | 80 | 690 | 215 | 268 | 58 | 101 | M6 | |
| WST Ⅱ 125/40.5-4×3ZH | 125 | 40.5 | ±5% | 3 | Middle part | 215 | 95 | 80 | 591 | 182 | 233 | 58 | 111 | M8 | |
| WST Ⅱ 125/40.5-6×5ZH | 125 | 40.5 | ±2×2.5% | 3 | Middle part | 215 | 95 | 80 | 765 | 240 | 291 | 58 | 111 | M8 | |
| WST Ⅱ 250/40.5-4×3ZH | 250 | 40.5 | ±5% | 3 | Middle part | 215 | 95 | 80 | 816 | 287 | 337 | 68 | 124 | M10 | |
| WST Ⅱ 250/40.5-6×5ZH | 250 | 40.5 | ±2×2.5% | 3 | Middle part | 215 | 95 | 80 | 1020 | 355 | 405 | 68 | 124 | M10 | |
Note
ZH - Double-layer combined tap changers
Tap changers with raised undersides can be manufactured upon customer request.
Tap changers rated at 63 and 125 A are suitable for transformer tank covers with thicknesses of 6 to 10 mm.
Tap changers rated at 250 and 300 A are suitable for transformer tank covers with thicknesses of 8 to 12 mm.
12~24kV Delta connection, series parallel transition with tap regulating,bar-type combined switch (installed on tank cover)
Type of tap-changer and installation size chart
| Type of combined tap-changer | Installation dimension (mm) | Holes on tank cover (mm) | ||||||
| H1 | H2 | H3 | L1 | L2 | L3 | Md | ||
| WST VI 63/24–5×2 WST V 63/24–4×3 |
175 | 75 | 75 | 221 | 256 | 101 | M6 | 2-Φ43 |
| WST VI 63/24–5×2 WST V 63/24–6×5 |
175 | 75 | 75 | 221 | 256 | 101 | M6 | 2-Φ43 |
| WST VI 125/24–5×2 WST V 125/24–4×3 |
180 | 75 | 75 | 231 | 276 | 111 | M8 | 2-Φ43 |
| WST VI 125/24–5×2 WST V 125/24–6×5 |
180 | 75 | 75 | 236 | 276 | 111 | M8 | 2-Φ43 |
12~24kV Delta connection, series parallel transition with tap regulating,bar-type combined switch (installed on tank cover)
Type of tap-changer and installation size chart
| Type of combined tap-changer | Installation dimension (mm) | Holes on tank cover (mm) | ||||||
| H1 | H2 | H3 | L1 | L2 | L3 | Md | ||
| WST VI 63/24-5 × 2 WST V 63/24-4 × 3 |
175 | 75 | 75 | 221 | 256 | 101 | M6 | 2-Φ43 |
| WST VI 63/24-5 × 2 WST V 63/24-6 × 5 |
175 | 75 | 75 | 221 | 256 | 101 | M6 | 2-Φ43 |
| WST VI 125/24-5 × 2 WST V 125/24-4 × 3 |
180 | 75 | 75 | 231 | 276 | 111 | M8 | 2-Φ43 |
| WST VI 125/24-5 × 2 WST V 125/24-6 × 5 |
180 | 75 | 75 | 236 | 276 | 111 | M8 | 2-Φ43 |
12~24kV series parallel transition with tap regulating, bar-type combined switch(installed on tank cover)
Type of tap-changer and installation size chart
| Type of combined tap-changer | Installation dimension (mm) | Holes on tank cover (mm) | |||||||
| H1 | H2 | H3 | L | L1 | L2 | L3 | Md | ||
| WST VI, 63/24-5×2 WST II, 63/24-4×3 WST II, 63/24-4×3 |
230 | 75 | 65 | 698 | 221 | 256 | 101 | M6 | 2-Φ43 |
| WST VI, 63/24-5×2 WST II, 63/24-6×5 WST II, 63/24-6×5 |
230 | 75 | 65 | 698 | 221 | 256 | 101 | M6 | 2-Φ43 |
| WST VI 125/24-5×2 WST II 125/24-4×3 WST II 125/24-4×3 |
285 | 95 | 80 | 698 | 221 | 256 | 111 | M8 | 2-Φ43 |
| WST VI 125/24-5×2 WST II 125/24-6×5 WST II 125/24-6×5 |
285 | 95 | 80 | 708 | 226 | 256 | 111 | M8 | 2-Φ43 |
| Combination switch model Type of combined tap-changer |
Installation dimension (mm) | Hatch Opening (mm) Holes on tank cover(mm) |
|||||||
| H1 | H2 | H3 | L | L1 | L2 | L3 | Md | ||
| WST VI263/24-5×2 WST II263/24-4×3 WST II263/24-4×3 |
210 | 75 | 55 | 638 | 206 | 226 | 92 | M6 | 2-Φ37 |
| WST VI263/24-5×2 WST II263/24-6×5 WST II263/24-6×5 |
210 | 75 | 55 | 638 | 206 | 226 | 92 | M6 | 2-Φ37 |
12~24kV series parallel transition with tap regulating,bar-type combined switch(installed on tank wall)
Type of tap-changer and installation size chart
| Combination switch model Type of combined tap-changer |
Installation dimension (mm) | Hole in the box wall (mm) Holes on tank cover(mm) |
|||||
| L1 | L2 | L3 | L4 | L5 | Md | ||
| WSTⅥ;63/24-5×2Z WSTⅠ;63/24-4×3Z WSTⅢ;63/24-4×3Z |
261 | 296 | 221 | 302 | 143 | M6 | 2-Φ43 |
| WSTⅥ;63/24-5×2Z WSTⅡ;63/24-6×5Z WSTⅢ;63/24-6×5Z |
261 | 296 | 221 | 302 | 143 | M6 | 2-Φ43 |
| WSTⅥ;125/24-5×2Z WSTⅡ;125/24-4×3Z WSTⅢ;125/24-4×3Z |
261 | 305 | 230 | 311 | 152 | M8 | 2-Φ43 |
| WSTⅥ;125/24-5×2Z WSTⅡ;125/24-6×5Z WSTⅢ;125/24-6×5Z |
270 | 305 | 230 | 311 | 152 | M8 | 2-Φ43 |
Keywords:
Combined tap changer
Learn more about the product
Submit your request or feedback
If you are interested in our products, please feel free to contact us to discuss potential collaboration.
Telephone
Email box
Address
No. 3 Fengming Road, Hairun Subdistrict, Sanmen County, Taizhou City, Zhejiang Province
Website Development:China Enterprise Dynamics Nantong|Tag
Online Inquiry