Single-phase bar-type tap changers (110 kV and below)
Category:
Service Hotline:+86-576-83379018
Online Inquiry
Product Details
This switch consists of a switching section and an operating rotary mechanism. It is suitable for oil-immersed power transformers with frequencies of 50 or 60 Hz, maximum voltages of 40.5 kV or 126 kV, and rated currents ranging from 200 to 1500 A. The switch is mounted on the transformer tank or the tank cover and is used for tap changing under no‑excitation conditions.
WDT linear single-phase de-energized bar tap-changer WDT I linear single-phase de-energized bar tap-changer
Type of tap-changer and installation size chart
| Switch model Type of tap-changer |
Rated current (A) Rated current(A) |
Maximum Equipment Voltage (kV) Highest voltage for equipment (kV) |
Voltage regulation range Range of voltage regulation |
Number of phases Number of phases |
Pressure-regulating section Regulating position |
Installation dimensions (mm) Install dimension (mm) |
Hatch Opening (mm) Holes on tank cover (mm) |
||||
| L | L1 | L2 | L3 | n | |||||||
| WDTⅠ200~800/40.5-3×3 | 200, 400 500, 630 800 |
40.5 | ±5% | 1 | Linear modulation Linear voltage regulating |
744 | 144 | 80 | 170 | 2 | Φ80 |
| WDTⅠ200~800/40.5-5×5 | ±2×2.5% | 888 | 288 | 80 | 170 | 4 | |||||
| WDTⅠ200~800/40.5-7×7 | ±3×2% | 1032 | 432 | 80 | 170 | 6 | |||||
| WDTⅠ200~800/40.5-9×9 | ±4×1.25% | 1196 | 576 | 100 | 170 | 8 | |||||
WDTII series de-energized tap-changer (200~800A) WDT II series de-energized tap-changer
Type of tap-changer and installation size chart
| Switch model Type of tap changer |
Rated Current (A) Rated current(A) |
Maximum Equipment Voltage (kV) Highest voltage for equipment (kV) |
Voltage regulation range Range of voltage regulation |
Number of phases Number of phases |
Pressure-regulating section Regulating position |
Installation dimensions (mm) Install dimension (mm) |
Hatch Opening (mm) Holes on tank cover (mm) |
|||||||
| L | L1 | L2 | H | H1 | ϕ D | |||||||||
| WDT II 1000~1500/40.5-4 × 3 | 1000, 1250, 1500 | 40.5 | ±5% | 1 | Central region Middle part |
776 | 516 | 72 | 103 | 44.5 | φ173 | φ80 | ||
| WDT II 1000~1500/40.5-6 × 5 | ±2 × 2.5% | 920 | 660 | 72 | ||||||||||
| WDT II 1000~1500/40.5-8 × 7 | ±3 × 2% | 1064 | 804 | 72 | ||||||||||
| WDT II 1000~1500/40.5-10 × 9 | ±4 × 1.25% | 1208 | 948 | 72 | ||||||||||
| WDT II 1000~1500/126-4 × 3 | 126 | ±5% | 848 | 588 | 96 | |||||||||
| WDT II 1000~1500/126-6 × 5 | ±2 × 2.5% | 1040 | 780 | 96 | ||||||||||
| WDT II 1000~1500/126-8 × 7 | ±3 × 2% | 1232 | 972 | 96 | ||||||||||
WDTII series de-energized tap-changer (1000~1500A) WDT II series de-energized tap-changer
Lead’s section and length of the bar switch
| Rated current (A) | Lead’s section mm² | Lead’s length (mm) |
| 200 | 70 | 700 |
| 400 | 150 | |
| 630 | 185 | |
| 800 | 240 | |
| 1000 (double leads) double leads | 185 | |
| 1250 (double leads) double leads | 185 | |
| 1500 (double leads) double leads | 240 |
Type of tap-changer and installation size chart
| Switch model Type of tap-changer |
Rated current (A) Rated current(A) |
Maximum equipment voltage (kV) Highest voltage for equipment (kV) |
Voltage regulation range Range of voltage regulation |
Number of phases Number of phases |
Pressure-regulating section Regulating position |
Installation dimensions (mm) Install dimension (mm) |
Hatch opening (mm) Holes on tank cover (mm) |
|||||||
| L | L1 | L2 | H | H1 | ΦD | |||||||||
| WDT II 200~400/40.5-4 × 3 | 200, 400 | 40.5 | ± 5% | 1 | Central region Middle part |
656 | 396 | 72 | 73.5 | 24.5 | Φ107 | Φ80 | ||
| WDT II 630~800/40.5-4 × 3 | 630, 800 | 100 | 34 | Φ127 | ||||||||||
| WDT II 200~400/40.5-6 × 5 | 200, 400 | ± 2 × 2.5% | 800 | 540 | 72 | 73.5 | 24.5 | Φ107 | ||||||
| WDT II 630~800/40.5-6 × 5 | 630, 800 | 100 | 34 | Φ127 | ||||||||||
| WDT II 200~400/40.5-8 × 7 | 200, 400 | ± 3 × 2% | 944 | 684 | 72 | 73.5 | 24.5 | Φ107 | ||||||
| WDT II 630~800/40.5-8 × 7 | 630, 800 | 100 | 34 | Φ127 | ||||||||||
| WDT II 200~400/40.5-10 × 9 | 200, 400 | ± 4 × 1.25% | 1088 | 828 | 72 | 73.5 | 24.5 | Φ107 | ||||||
| WDT II 630~800/40.5-10 × 9 | 630, 800 | 100 | 34 | Φ127 | ||||||||||
| WDT II 200~400/126-4 × 3 | 200, 400 | 126 | ± 5% | 728 | 468 | 96 | 73.5 | 24.5 | Φ107 | |||||
| WDT II 630~800/126-4 × 3 | 630, 800 | 100 | 34 | Φ127 | ||||||||||
| WDT II 200~400/126-6 × 5 | 200, 400 | ± 2 × 2.5% | 920 | 660 | 96 | 73.5 | 24.5 | Φ107 | ||||||
| WDT II 630~800/126-6 × 5 | 630, 800 | 100 | 34 | Φ127 | ||||||||||
| WDT II 200~400/126-8 × 7 | 200, 400 | ± 3 × 2% | 1112 | 852 | 96 | 73.5 | 24.5 | Φ107 | ||||||
| WDT II 630~800/126-8 × 7 | 630, 800 | 100 | 34 | Φ127 | ||||||||||
| WDT II 200~400/126-10 × 9 | 200, 400 | ± 4 × 1.25% | 1304 | 1044 | 96 | 73.5 | 24.5 | Φ107 | ||||||
| WDT II 630~800/126-10 × 9 | 630, 800 | 100 | 34 | Φ127 | ||||||||||
The control lever is 1 meter long.
If customers have any special requirements, please specify them when placing your order.
If the customer has some special requirements, please detailed in ordering.
W(D+L)TII series de-energized strip tap-changer (vertical)
Type of tap-changer and installation size chart
| Switch model Type of tap-changer |
Rated Current (A) Rated current |
Maximum Equipment Voltage (kV) Highest voltage for equipment (kV) |
Voltage regulation range Range of voltage regulation |
Number of phases Number of phases |
Installation dimensions (mm) Install dimension (mm) |
Hatch Opening (mm) Holes on tank cover (mm) |
|||||||
| L | L1 | L2 | L3 | L4 | H | H1 | ΦD | ||||||
| W(D+L)T Ⅱ 200/40.5-4 × 3AL | 200 | 40.5 | ± 5% | 1+2 | 584 | 324 | 48 | 998 | 324 | 68.5 | 24.5 | Φ107 | Φ80 |
| W(D+L)T Ⅱ 200/40.5-6 × 5AL | 200 | ± 2 × 2.5% | 680 | 420 | 48 | 1190 | 420 | 68.5 | 24.5 | Φ107 | |||
| W(D+L)T Ⅱ 200/40.5-8 × 7AL | 200 | ± 3 × 2% | 776 | 516 | 48 | 1382 | 516 | 68.5 | 24.5 | Φ107 | |||
| W(D+L)T Ⅱ 200/126-4 × 3AL | 200 | 126 | ± 5% | 728 | 468 | 96 | 1416 | 533 | 68.5 | 24.5 | Φ107 | ||
| W(D+L)T Ⅱ 200/126-6 × 5AL | 200 | ± 2 × 2.5% | 920 | 660 | 96 | 1800 | 725 | 68.5 | 24.5 | Φ107 | |||
| W(D+L)T Ⅱ 200/126-8 × 7AL | 200 | ± 3 × 2% | 1112 | 852 | 96 | 2184 | 917 | 68.5 | 24.5 | Φ107 | |||
The distribution lead has a cross-sectional area of 70 mm² and a length of 700 mm. For the 35 kV lead, the single-sided insulation thickness is 3 mm; for the 110 kV lead, it is 6 mm.
Standard lead section is 70mm²,700mm long. 35kv lead is packed with insulation paper 3mm thickness,110kv with thickness of 6mm.
Keywords:
Single-phase bar-type tap changers (110 kV and below)
Learn more about the product
Submit your request or feedback
If you are interested in our products, please feel free to contact us to discuss potential collaboration.
Telephone
Email box
Address
No. 3 Fengming Road, Hairun Subdistrict, Sanmen County, Taizhou City, Zhejiang Province
Website Development:China Enterprise Dynamics Nantong|Tag