Electric non-excitation tap changer


Service Hotline:+86-576-83379018

product Online Inquiry

Product Details


Rated voltage of 66 kV (maximum equipment voltage of 72.5 kV) and below, with a rated current of 2000 A and below.

This switch consists of an electric actuator, the switch body, and an electric controller. It is available in two configurations—vertical and horizontal (W)—and is suitable for oil-immersed furnace transformers with a maximum rated voltage of 72.5 kV or less and a rated current of 2000 A or less. Tap changing is performed under no‑excitation conditions and can be operated either electrically or manually.

Controller installation size:

Power-driven switch controller cable with 20 m
The tap-changer can be designed according to the user's request!

Circular (U) vertical electric de-energized tap-changer

Type of tap-changer and installation size chart

Switch Type
Type of changer
Rated current
(A)
Rated current
(A)
Maximum Equipment Voltage (kV)
Highest voltage for equipment
(kV)
Pressure-regulating section
Regulating position
Installation dimension (mm)
H3 H2 H1 H Md Φd Φd1 Φd2 Φd3 Φd4 n  
WSLD Ⅱ 200~630/12-4 × 3~10 × 9U4 200, 400, 630 12 Central region
Middle part
120 187 580 860 Md=M12 for a rated current of 200 A; Md=M16 for a rated current of 400 A; Md=M18 for a rated current of 630 A. 370 380 425 460 380 18  
WSLD Ⅲ 200~630/12-5 × 5~ 9 × 9U4 Neutral point
Neutral point
 
WSLD Ⅱ 200~630/40.5-4 × 3~10 × 9U4 40.5 Central region
Middle part
170 240 780 1060  
WSLD Ⅲ 200~630/40.5~5 × 5~9 × 9U4 Neutral point
Neutral point
 
WSLD Ⅱ 200~630/12-11 × 10~15 × 14U5 12 Central region
Middle part
120 187 580 860 450 460 520 550 380 20  
WSLD Ⅲ 200~630/12-11 × 11~15 × 15U5 Neutral point
Neutral point
 
WSLD Ⅱ 200~630/40.5-11 × 10~15 × 14U5 40.5 Central region
Middle part
170 240 780 1060  
WSLD Ⅲ 200~630/40.5-11 × 11~15 × 15U5 Neutral point
Neutral point
 

A model designation followed by “U5” indicates that the center-to-center diameter of the mounting holes on the cover of this circular tap changer is 520 mm.

The designation “U4” appended to the model number indicates that the center-to-center diameter of the mounting holes on the cover of this circular tap changer enclosure is 425 mm.

The model add-on U5 means the diameter of the cover's hole of this tap-changer is 520mm;

The model add-on U4 means the diameter of the cover 's hole of this tap-changer is 425mm.

Circular (U) and horizontal (W) de-energized tap-changer

Type of tap-changer and installation size chart AX

Switch Type
Type of changer
Rated Current (A)
Rated current(A)
Maximum Equipment Voltage (kV)
Highest voltage for equipment (kV)
Pressure-regulating section
Regulating position
Installation dimension (mm)
L1 L2 L3 L4 H1 H2 Md
WSLD Ⅱ 200~630/12-4×3~8×7WU4 200, 400, 630 12 Central region
Middle part
120 140 544 620 150 355

The current is 400 A, and Md = M12.

The rated current is 630 A, and the model is Md=M16.

WSLD Ⅲ 200~630/12-3×3~7×7WU4 Neutral point
Neutral point
WSLD Ⅱ 200~630/40.5-4×3~8×7WU4 40.5 Central region
Middle part
170 190 744 820
WSLD Ⅲ 200~630/40.5--3×3~7×7WU4 Neutral point
Neutral point

Keywords:

Electric non-excitation tap changer

Learn more about the product

Submit your request or feedback

If you are interested in our products, please feel free to contact us to discuss potential collaboration.